Functions
2.11 Undervoltage and Overvoltage Protection (optional)
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
169
2.11.5 Information List
3758 CURR.SUP. Uphe< ON
OFF
ON Current supervision (Uph-e)
3759A Uph-e<(<) RESET 1.01 .. 1.20 1.05 Uph-e<(<) Reset ratio
3761 Uph-ph<(<) OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode Uph-ph under-
voltage prot.
3762 Uph-ph< 1.0 .. 175.0 V; 0 50.0 V Uph-ph< Pickup
3763 T Uph-ph< 0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-ph< Time Delay
3764 Uph-ph<< 1.0 .. 175.0 V; 0 17.0 V Uph-ph<< Pickup
3765 T Uphph<< 0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph< ON
OFF
ON Current supervision (Uph-ph)
3769A Uphph<(<) RESET 1.01 .. 1.20 1.05 Uph-ph<(<) Reset ratio
3771 U1<(<) OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode U1 undervoltage
prot.
3772 U1< 1.0 .. 100.0 V; 0 30.0 V U1< Pickup
3773 T U1< 0.00 .. 100.00 sec; ∞ 2.00 sec T U1< Time Delay
3774 U1<< 1.0 .. 100.0 V; 0 10.0 V U1<< Pickup
3775 T U1<< 0.00 .. 100.00 sec; ∞ 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1< ON
OFF
ON Current supervision (U1)
3779A U1<(<) RESET 1.01 .. 1.20 1.05 U1<(<) Reset ratio
No. Information Type of In-
formation
Comments
234.2100 U<, U> blk IntSP U<, U> blocked via operation
10201 >Uph-e>(>) BLK SP >BLOCK Uph-e>(>) Overvolt. (phase-earth)
10202 >Uph-ph>(>) BLK SP >BLOCK Uph-ph>(>) Overvolt (phase-phase)
10203 >3U0>(>) BLK SP >BLOCK 3U0>(>) Overvolt. (zero sequence)
10204 >U1>(>) BLK SP >BLOCK U1>(>) Overvolt. (positive seq.)
10205 >U2>(>) BLK SP >BLOCK U2>(>) Overvolt. (negative seq.)
10206 >Uph-e<(<) BLK SP >BLOCK Uph-e<(<) Undervolt (phase-earth)
10207 >Uphph<(<) BLK SP >BLOCK Uphph<(<) Undervolt (phase-phase)
10208 >U1<(<) BLK SP >BLOCK U1<(<) Undervolt (positive seq.)
10215 Uph-e>(>) OFF OUT Uph-e>(>) Overvolt. is switched OFF
10216 Uph-e>(>) BLK OUT Uph-e>(>) Overvolt. is BLOCKED
10217 Uph-ph>(>) OFF OUT Uph-ph>(>) Overvolt. is switched OFF
10218 Uph-ph>(>) BLK OUT Uph-ph>(>) Overvolt. is BLOCKED
10219 3U0>(>) OFF OUT 3U0>(>) Overvolt. is switched OFF
Addr. Parameter Setting Options Default Setting Comments

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD610 and is the answer not in the manual?

Siemens SIPROTEC 7SD610 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD610
CategoryRelays
LanguageEnglish

Related product manuals