1.3 Characteristics
General Features
Powerful 32-bit microprocessor system
Complete digital processing of measured values and control, from the sampling of the analog input values,
the processing and organization of the communication between devices up to the closing and tripping com-
mands to the circuit breakers
Complete galvanic separation and interference immunity of the internal processing circuits from the mea-
surement, control, and power supply circuits by analog input transducers, binary inputs and outputs and the
DC/DC or AC/DC converters
Suited for lines with 2 ends, even with transformers in the protected zone (order option)
Simple device operation using the integrated operator panel or a connected personal computer with operator
guidance
Storage of fault indications and instantaneous values for fault recording
Differential Protection
Differential protection system for 2 ends with digital protection data transmission
Protection for all types of short-circuits in systems with any neutral-point treatment conditioning
Reliable differentiation between load and fault conditions also in high-resistant, current-weak faults by adap-
tive measuring procedures
High sensitivity in case of weakly loaded system, extreme stability against load jumps and power swings
Phase-selective measurement ensures that the pickup sensitivity is independent of the fault type
Suited for transformers in the protected zone (order variant)
Detection of high-resistance, weak-current faults due to high sensitivity of the protection functions
Insensitive to inrush and charging currents – also for transformers in the protected zone – and to higher-
frequency transient processes
High stability also for different current transformer saturation
Adaptive stabilisation that is automatically derived from the measured quantities and the configured current
transformer data
Fast, phase segregated tripping also on weak or zero infeed ends (breaker intertrip)
Low dependence on frequency
Digital protection data transmission; communication between devices via dedicated communication links (in
general optical fibre) or a communication system
Communication possible via a single copper wire pair (typically 8 km, max. up to 30 km, depending on cable
type used)
Synchronization via GPS possible, resulting in automatic correction of transmission time differences thus
increasing once more the sensitivity
Permanent monitoring of the protection data transmission concerning disturbance, failure or transfer time
deviations in the transmission network with automatic transfer time correction
Phase segregated tripping possible (for operation with single-pole or single-and three-pole auto-reclosure)
(order variant)