EasyManuals Logo

Siemens SIPROTEC 7SD610 User Manual

Siemens SIPROTEC 7SD610
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #204 background imageLoading...
Page #204 background image
Functions
2.15 Monitoring Functions
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
204
A wire break is signalled under the following conditions:
• A suspected local wire break has been detected.
• The logic for detecting the circuit breaker position (see Section 2.16.1, Detection of the Circuit Breaker Po-
sition) does not signal an open circuit breaker pole. Wire break detection is not possible if the circuit breaker
is open. If the breaker position cannot be determined, a closed circuit breaker is assumed.
• In all voltage channels, no jump must have been detected. Jumps in these channels indicate a genuine
power system fault.
• In the other current channels, there must have been no jump without wire break detection. Jumps in the other
current channels also suggest a power system fault, except if a suspected local wire break has been detect-
ed for the affected phases.
• The device at the other end of the protected object must not have signalled a jump. The jump information is
transferred together with the differential protection measurements, so that this information is available simul-
taneously with the first run of the differential protection after the jump.
• In the phase, also the devices at the other end of the protected object must not have measured a phase
current of more than 2 I
N
. A phase current of such a magnitude is a certain indicator of a power system fault.
A wire break detected by the aforementioned criteria is transmitted to the device at the other end of the pro-
tected object and immediately prompts a broken wire report. The differential protection function will also be
blocked provided that it has been configured accordingly.
In the event of a local wire break, the message „broken wire I
Lx
“ (no. 290, 291, 292) is generated, whereas
when the broken wire is detected at the other end of the protected object, the message is „broken wire at the
other end I
Lx
“ (no. 297, 298, 299). If the broken wire monitoring is deactivated, the message 295 „Broken
wire OFF“ ensues.
The broken wire monitoring is reset by the return of the phase current (I
Lx
> 0.05 I
N
) or by the binary input
message 3270 „>RESET BW“. In 1-1/2 circuit breaker arrangements, the function can only be reset by the
binary input message because the current magnitude is no reliable criterion for a reset of the broken wire mon-
itoring.
If the communication between the devices is disturbed, the device operates in emergency operation. The dif-
ferential protection is not active. The wire break detection then operates only with the locally available informa-
tion. Multipole wire break is not indicated in emergency operation.
It has to be observed that electronic test devices do not behave like a circuit breaker so that pickup can occur
during such tests.

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD610 and is the answer not in the manual?

Siemens SIPROTEC 7SD610 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD610
CategoryRelays
LanguageEnglish

Related product manuals