- Setting Group C is active (P-
GrpC act)
Change Group IntSP on
off
* * LED BO 192 25 1 Yes
- Setting Group D is active (P-
GrpD act)
Change Group IntSP on
off
* * LED BO 192 26 1 Yes
- Fault Recording Start (FltRecSta) Osc. Fault Rec. IntSP on
off
*mLEDBO
- CB1-TEST trip/close - Only L1
(CB1tst L1)
Test in g - * *
- CB1-TEST trip/close - Only L2
(CB1tst L2)
Test in g - * *
- CB1-TEST trip/close - Only L3
(CB1tst L3)
Test in g - * *
- CB1-TEST trip/close Phases
L123 (CB1tst 123)
Test in g - * *
- Controlmode REMOTE (ModeR-
EMOTE)
Cntrl Authority IntSP on
off
* LED BO
- Control Authority (Cntrl Auth) Cntrl Authority IntSP on
off
* LED BO 101 85 1 Yes
- Controlmode LOCAL (ModeLO-
CAL)
Cntrl Authority IntSP on
off
* LED BO 101 86 1 Yes
- Breaker (Breaker) Control Device CF_D
12
on
off
* BO 240 160 20
- Breaker (Breaker) Control Device DP on
off
* BI CB 240 160 1 Yes
- Disconnect Switch (Disc.Swit.) Control Device CF_D
2
on
off
* BO 240 161 20
- Disconnect Switch (Disc.Swit.) Control Device DP on
off
* BI CB 240 161 1 Yes
- Earth Switch (EarthSwit) Control Device CF_D
2
on
off
* BO 240 164 20
- Earth Switch (EarthSwit) Control Device DP on
off
* BI CB 240 164 1 Yes
- Interlocking: Breaker Open (Brk
Open)
Control Device IntSP * * *
- Interlocking: Breaker Close (Brk
Close)
Control Device IntSP * * *
- Interlocking: Disconnect switch
Open (Disc.Open)
Control Device IntSP * * *
- Interlocking: Disconnect switch
Close (Disc.Close)
Control Device IntSP * * *
- Interlocking: Earth switch Open
(E Sw Open)
Control Device IntSP * * *
- Interlocking: Earth switch Close
(E Sw Cl.)
Control Device IntSP * * *
- Q2 Open/Close (Q2 Op/Cl) Control Device CF_D
2
on
off
* BO 240 162 20
- Q2 Open/Close (Q2 Op/Cl) Control Device DP on
off
* BI CB 240 162 1 Yes
- Q9 Open/Close (Q9 Op/Cl) Control Device CF_D
2
on
off
* BO 240 163 20
- Q9 Open/Close (Q9 Op/Cl) Control Device DP on
off
* BI CB 240 163 1 Yes
- Fan ON/OFF (Fan ON/OFF) Control Device CF_D
2
on
off
* BO 240 175 20
- Fan ON/OFF (Fan ON/OFF) Control Device DP on
off
* BI CB 240 175 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents

Other manuals for Siemens SIPROTEC 7SD610

Related product manuals