Appendix
A.8 Information List
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
418
7222 Backup O/C TRIP I> (O/C TRIP
I>)
Back-Up O/C OUT * on * LED BO 64 122 2 No
7223 Backup O/C TRIP Ip (O/C TRIP
Ip)
Back-Up O/C OUT * on * LED BO 64 123 2 No
7235 O/C I-STUB TRIP (I-STUB TRIP) Back-Up O/C OUT * on * LED BO 64 135 2 No
7236 Backup O/C TRIP I> directional
(O/C TRIP I>Dir.)
Back-Up O/C OUT * on * LED BO 64 136 2 No
7237 Backup O/C Pickup Ip directional
(O/C TRIP IpDir.)
Back-Up O/C OUT * on * LED BO 64 137 2 No
7240 Backup O/C L1 forward direction
(O/C L1 forward)
Back-Up O/C OUT * on * LED BO 64 140 2 No
7241 Backup O/C L2 forward direction
(O/C L2 forward)
Back-Up O/C OUT * on * LED BO 64 141 2 No
7242 Backup O/C L3 forward direction
(O/C L3 forward)
Back-Up O/C OUT * on * LED BO 64 142 2 No
7243 Backup O/C 3I0 forward direction
(O/C 3I0 forward)
Back-Up O/C OUT * on * LED BO 64 143 2 No
7244 Backup O/C L1 reverse direction
(O/C L1 reverse)
Back-Up O/C OUT * on * LED BO 64 144 2 No
7245 Backup O/C L2 reverse direction
(O/C L2 reverse)
Back-Up O/C OUT * on * LED BO 64 145 2 No
7246 Backup O/C L3 reverse direction
(O/C L3 reverse)
Back-Up O/C OUT * on * LED BO 64 146 2 No
7247 Backup O/C 3I0 reverse direction
(O/C 3I0 reverse)
Back-Up O/C OUT * on * LED BO 64 147 2 No
7248 Backup O/C forward direction
(O/C Dir.forward)
Back-Up O/C OUT * * * LED BO
7249 Backup O/C reverse direction
(O/C Dir.reverse)
Back-Up O/C OUT * * * LED BO
7325 CB1-TEST TRIP command -
Only L1 (CB1-TESTtrip L1)
Testing OUT on
off
* * LED BO 153 25 1 Yes
7326 CB1-TEST TRIP command -
Only L2 (CB1-TESTtrip L2)
Testing OUT on
off
* * LED BO 153 26 1 Yes
7327 CB1-TEST TRIP command -
Only L3 (CB1-TESTtrip L3)
Testing OUT on
off
* * LED BO 153 27 1 Yes
7328 CB1-TEST TRIP command L123
(CB1-TESTtrip123)
Testing OUT on
off
* * LED BO 153 28 1 Yes
7329 CB1-TEST CLOSE command
(CB1-TEST close)
Testing OUT on
off
* * LED BO 153 29 1 Yes
7345 CB-TEST is in progress (CB-
TEST running)
Testing OUT on
off
* * LED BO 153 45 1 Yes
7346 CB-TEST canceled due to Power
Sys. Fault (CB-TSTstop FLT.)
Testing OUT_
Ev
on *
7347 CB-TEST canceled due to CB
already OPEN (CB-TSTstop
OPEN)
Testing OUT_
Ev
on *
7348 CB-TEST canceled due to CB
was NOT READY (CB-TSTstop
NOTr)
Testing OUT_
Ev
on *
7349 CB-TEST canceled due to CB
stayed CLOSED (CB-TSTstop
CLOS)
Testing OUT_
Ev
on *
7350 CB-TEST was successful (CB-
TST .OK.)
Testing OUT_
Ev
on *
10201 >BLOCK Uph-e>(>) Overvolt.
(phase-earth) (>Uph-e>(>) BLK)
Voltage Prot. SP * * * LED BI BO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation