3 Mounting and Commissioning
246
7UM61 Manual
C53000-G1176-C127-3
Table 3-8 Jumper setting of control voltages of binary inputs BI1 to BI8 on Input/Output
module module C– I/O–1 in the 7UM612
1)
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
2)
Factory settings for devices with rated power supply voltages 110 VDC to 220 VDC and
115/230 VAC
3)
Use only with control voltages 220 VDC or 250 VDC
Jumpers X71, X72 and X73 on the C–I/O–1 board serve to set the bus address. The
jumpers must not be changed. The following table lists the jumper presettings.
The installation locations of the boards are shown in Figures 3-1 to 3-2 .
Table 3-9 Module address jumper setting of input/output module C-I/O-1 for 7UM612
Binary Inputs Jumper 19 V Threshold
1)
88 V Threshold
2)
176 V Threshold
3)
BI8 X21/X22 L M H
BI9 X23/X24 L M H
BI10 X25/X26 L M H
BI11 X27/X28 L M H
BI12 X29/X30 L M H
BI13 X31/X32 L M H
BI14 X33/X34 L M H
BI15 X35/X36 L M H
Jumper Factory Setting
X71 L
X72 H
X73 H
www . ElectricalPartManuals . com