Product description
3.4 3RA28 function modules
SIRIUS 3RA28 function modules for mounting on 3RT2 contactors
24 Manual, 02/2019, A5E03656507620A/RS-AD/005
3.4 3RA28 function modules
Function module for direct-on-line start (electronic timing relays with semiconductor output/solid-state
time-delay auxiliary switches)
Time range selector switch:
Sets the time base (1 s, 10 s, 100 s)
Operating time adjustment switch:
Sets the relative time (5 to 100%)
Indicates the switching state of the contactor
5 Screw/spring-loaded terminals: The terminals are available as both screw-type and
spring-loaded connections.
Figure 3-2 Electronic timing relays with semiconductor output/solid-state time-delay auxiliary
switches
Function module for star-delta (wye-delta) start
The function module for star-delta (wye-delta) start comprises a basic module with integrated
control logic and two coupling modules of the same type.
Basic module with integrated control logic
3 Coil control: Basic module: Voltage measurement at the line contactor
Coupling module: Controls the contactor below
Electrical connection of modules
Slot for connecting cable:
Routes the supply voltage and electrical interlock
Time range selector switch:
Sets the time base (10 s, 30 s, 60 s)
Operating time adjustment switch:
Sets the relative time (5 to 100%)
Indicates the switching state of the contactor
Figure 3-3 Basic module and coupling modules for the contactor assembly for star-delta (wye-delta)
start