The 3UG4633 voltage monitoring relays have a display and are parameterized with three keys.
You will 󹪝nd the setting ranges and factory settings of the available parameters in Chapter
"Operation (Page 210)."
You will 󹪝nd a description of the individual parameters in Chapter "Parameters (Page 281)."
Monitoring
Output relay K1 responds in accordance with the set relay switching behavior (closed-circuit
principle NC or open-circuit principle NO).
An output change-over contact is available as a signaling contact.
If the voltage is switched on, the display will show the current measured value and a symbol for
monitoring for voltage overshoot, voltage undershoot, or range monitoring.
Startup delay
To be able to start a drive, the output relay switches to the correct state during the ON-delay time
(onDel) depending on the selected open-circuit principle or closed-circuit principle, even if the
measured value is still under the set value.
Tripping delay
If the measured value overshoots or undershoots the set threshold after expiry of the ON-delay
time (onDel), the set tripping delay time (Del) and the relay symbol will 󹪞ash. After expiry of this
time, the output relays change the switching state. On the display, the current measuring value
and the symbol for undershoot or overshoot 󹪞ash.
You will 󹪝nd the switching states of the output relay below in the section entitled "Function
diagrams" and in Chapter "Diagnostics (Page 212)."