EasyManua.ls Logo

Siemens SIRIUS 3UG4 - Diagnostics; Diagnostics with LED

Siemens SIRIUS 3UG4
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function diagrams 3UG4512
Phase failure Incorrect phase sequence
11/14
L1-L2-L3L2-L3L1-L2-L3
11/12
21/24
21/22
OFF OFFON
LED
1
2
11/14
11/12
21/24
21/22
L3-L2-L1
FLASH OFFOFF
LED
1
2
Red Red
Phase failure Phase sequence
6.3.3 Diagnostics
6.3.3.1 Diagnostics with LED
Status display
The following information about the operating state is displayed on the 3UG4512 line
monitoring relay:
Operating state LED State of the output relays
Coil symbol (green) Phase failure / phase se‐
quence (red)
12/ 11/ 14
22/ 21/ 24
Supply voltage not present
O󹪜 O󹪜
Supply voltage present
Correct phase sequence
All phases available
On O󹪜
Supply voltage present
Incorrect phase sequence
On 󹪞ashing
Supply voltage present
Phase failure
On On
3UG4.1 line monitoring relay
6.3 3UG4512 line monitoring relay
SIRIUS 3UG4 / 3RR2 monitoring relay
Equipment Manual, 07/2021, NEB927043002000/RS-AD/005 89

Table of Contents

Related product manuals