Scaling factor
The "scaling factor" parameter allows the user to set the number of pulses per revolution
provided by the pulse encoder. This allows the revolutions per minute to be read direct on the
display.
Possible indications on the display: Scale
Stabilization delay
An output is only switched to the "correct position" after switching on the supply voltage if all
monitored measured values are stable for the duration of the stabilization delay. The monitoring
functions are active within the stabilization delay. A threshold overshoot or undershoot in this
time does not result in a fault, but instead in restarting of the stabilization delay.
The stabilization delay starts in the following cases:
At Power‑ON
Reapplication of the supply voltage (Power‑ON) of the device after
disconnection of the current 󹪞ow (zero current).
At manual reset
A fault is acknowledged by a manual reset. After this, the device responds in the same way
as
when the supply voltage is connected.
Starting the stabilization delay via IO‑Link
The stabilization time can also be started through the process image of the outputs (PIQ) by
setting the control command "Start stabilization time."
The "Stabilization time" parameter is set either locally using the three keys on the device, or via
IO‑Link. The requirements governing the starting of the stabilization delay (Power‑ON and/or
manual reset) can only be modi󹪝ed via IO‑Link.
Parameters
SIRIUS 3UG4 / 3RR2 monitoring relay
Equipment Manual, 07/2021, NEB927043002000/RS-AD/005 289