Function Monitoring relays
3UG45 3UG46
01 11 12 13 8 14 15 16 17 18 31 32 33 21 22 41 25 51
Monitoring for N conductor
failure
Automatic direction of rotation
correction in the case of incorrect
phase sequence
Power factor monitoring and current monitoring
Monitoring for undercurrent 1p 1p 1p
Monitoring for overcurrent 1p 1p 1p
Active current monitoring
Apparent current monitoring
Power factor monitoring
Fault current monitoring/insulation monitoring
Monitoring for fault current/
ground fault
Insulation monitoring
Filling level monitoring
Monitoring for 󹪝lling level over‐
shoot / resistance overshoot
Monitoring for 󹪝lling level under‐
shoot / resistance undershoot
Speed monitoring
Monitoring for speed overshoot
Monitoring for speed undershoot
Rated control supply voltage
Self-powered, without auxiliary
voltage
Externally powered, with auxili‐
ary voltage
✓: Function available
1p: Monitoring is 1-phase
3p: Monitoring is 3-phase
— : Function not available
○: Function available with limitations
1)
Detection causes problems with regenerative power recovery.
2)
By monitoring the voltage thresholds.
True root mean square measurement (tRMS) / use with frequency converters:
The monitoring relays work with an electronic measuring method which calculates the actual
(e󹪜ective) value of a measured value (tRMS), regardless of whether the measured variable's
waveform is purely sinusoidal or distorted.
System overview
3.5 Overview of the functions
SIRIUS 3UG4 / 3RR2 monitoring relay
42 Equipment Manual, 07/2021, NEB927043002000/RS-AD/005