level
Parameters Setting range Increment Factory setting
Minimum value Maximum value
"SET" Load current monitor‐
ing (apparent cur‐
rent I
s
/active current I
p
)
I
s
or I
p
-- I
s
"SET" Relay switching behav‐
ior (closed-circuit prin‐
ciple NC / open-circuit
principle NO)
NC or NO -- NC
1)
3RR2241 current monitoring relay
2)
3RR2242 current monitoring relay
3)
3RR2243 current monitoring relay
Note
The "current overshoot" or "current undershoot" monitoring mode is de󹪝ned with the setting
OFF for the upper and lower threshold.
Note
Deactivating monitoring
If the upper and lower threshold values are deactivated (OFF), monitoring will cease for:
Current overshoot
Current undershoot
Blocking current
The following parameters continue to be monitored:
Fault current (if activated)
Incorrect phase sequence (if activated)
Phase failure
The up-to-date measured value is displayed permanently.
The parameters are described in the Chapter "Parameters (Page 281)".
Menu-based operation is described in the Chapter "Menu-based operation (Page 44)".
3RR2 current monitoring relays
4.5 3RR22 current monitoring relays
SIRIUS 3UG4 / 3RR2 monitoring relay
66 Equipment Manual, 07/2021, NEB927043002000/RS-AD/005