Profibus Communication
B.8 Device Database File (GSD)
SITRANS F M TRANSMAG 2
Operating Instructions, 11/2009, A5E00102775-07
103
; If you don_t want to get the measuring value of a certain module ; from the device with the
input data, use Free place for this module ; instead of another identifier.
;
; For the module 1 you have the choice between these different ; identifiers:
;
; - Free Place
; - Short identifier format (identifier byte)
; - Long identifier format (extended identifier)
;
; For the modules 2, 3 and 4 you have the choice between these ; different identifiers:
;
; - Free Place
; - Long identifier format (extended identifier)
; - Long identifier format, resettable (extended identifier)
; With the "resettable" format it is possible to reset the totalizer,
; transmitting suitable output data to the device.
;---------------------------------------------------------------------
; Free place - usable for each module instead of another identifier
;---------------------------------------------------------------------
Module = "Free place" 0x00
0
EndModule
;---------------------------------------------------------------------
; Module 1 - Flow
;---------------------------------------------------------------------
Module = "Flow" 0x94
1
EndModule
;---------------------------------------------------------------------
; Module 2 - Quantity net
;---------------------------------------------------------------------
Module = "Quantity net" 0x41, 0x84, 0x85
2
EndModule
Module = "Resettable quantity net" 0xC1, 0x80, 0x84, 0x85
3