7.5 Function Group Device Outputs
SITRANS F M TRANSMAG 2
56 Operating Instructions, 11/2009, A5E00102775-07
CAUTION
At high inductive loads, the digital output must be protected against transient overvoltage
with a suitable external recovery diode.
The electronic fuse is tripped in the event of overloading. The recovery time of the fuse is a
few minutes. The relay contact is open in the no-load state.
Digital input (Menu item 4.3)
The digital input is available with the device variant 7ME5034-2xxxx (Hart communication
and digital input). You have the following setting options in this menu:
Function, menu item 4.3.1
By applying an external power supply, you can create a switching input, for example
using a switch (see also Figure 5-12). You have the following possibilities depending on
the configuration:
Set the measured value to "0" (all outputs and displays are reset to zero and the
totalizers are stopped
Reset the forwards totalizer
Reset the reverse totalizer
Reset the net totalizer
Reset all totalizers
elektronische
Sicherung
Ri 3k
ext. Versorgung
max. 30 V
ext. Schalter
+
-
4
3
5V
Electronic fuse
External switch
External supply 11 ... 24 V (max. 30 V)
Figure 7-9 Circuit diagram of digital input
Signal type, menu item 4.3.2
You can determine the signal type (high-active) with this.