2.9 Cyclic data exchange
A central controller that cyclically exchanges data with slave devices on a PROFIBUS network
is called a Master class 1 device. A GSD file is normally used when setting up the master to
exchange data with the slave device. The order of the data in the cyclic message is the same
as the order in the GSD file.
Each device supports three different GSD files. The manufacturer specific and the
manufacturer independent Profile 3 GSD-files are described in the following.
Supported GSD files
The DP/ PA version of the SITRANS FCT030 supports the following GSD files
DP version PA version
GSD Description GSD Description
si0181CB.gsd SITRANS FC330 / FC430 /
FCT030 manufacturer specif‐
ic GSD for DP
si0181CC.gsd SITRANS FC330 / FC430 /
FCT030 manufacturer specif‐
ic GSD for PA
si018127.gsd SITRANS FC MASS6000 DP si018128.gsd SITRANS FC MASS6000 PA
pa05B333.gsd PA Profile 4 Specific GSD for
Coriolis flow devices DP
(Mass flow, Density, Medium
temperature, Totalizer 1 -
Mass)
pa15B333.gsd PA Profile 4 Specific GSD for
Coriolis flow devices
PA(Mass flow, Density, Medi‐
um temperature, Totalizer 1 -
Mass)
pa039700.gsd PA Profile 3 Specific GSD (1
Analog Input, DP)
pa139700.gsd PA Profile 3 Specific GSD (1
Analog Input, PA)
pa039701.gsd PA Profile 3 Specific GSD (2
Analog Inputs, DP)
pa039701.gsd PA Profile 3 Specific GSD (2
Analog Inputs, DP)
pa039702.gsd PA Profile 3 Specific GSD (3
Analog Inputs, 1 Totalizer,
DP)
pa039702.gsd PA Profile 3 Specific GSD (3
Analog Inputs, 1 Totalizer,
DP)
pa039742.gsd PA Profile 3 Specific GSD (3
Analog Inputs, 1 Totalizer,
DP)
pa039742.gsd PA Profile 3 Specific GSD (3
Analog Inputs, 1 Totalizer,
DP)
Modules for cyclic data exchange, Manufacturer specific GSD
Table 2-1 Manufacturer specific GSD
Slot Module Description
Input (from device to
master)
Output (from master to device)
1 Mass Flow Byte 0....3
Byte 4
Mass flow
Mass Flow status
-
2 Density Byte 0....3
Byte 4
Density
Density Status
-
Communication
2.9 Cyclic data exchange
FCT030 Profibus (From firmware 4.0)