Return the device to operation
1. Restore power to the device.
2. Check that the device starts up as expected. If possible watch the display during startup
and observe the device versions for consistency.
2.6 Connecting the Profibus (CH1)
WARNING
Passive channels only
Channel 1 power supply must be separated from that for channels 2 to 4.
Signal return (or common) can be joined.
1. Remove cap and ferrule from cable gland and slide onto cable.
2. Push cable through open gland and cable path.
3. Restore ferrule and tighten cap to lightly hold cable in place.
4. Signal cable screen is folded back over outer sheath and grounded beneath cable clamp.
5. Connect wires to terminals using wiring tool, field mount transmitter
PROFIBUS DP/PA
In + (B)
In - (A)
Out + (B)
Out - (A)
Functional Earth
Communication
2.6 Connecting the Profibus (CH1)
FCT030 Profibus (From firmware 4.0)
12 Function Manual, 06/2018, A5E39931906-AB