Default unit selection of Totalizers
The device provides the possibility to select units for each
totalizer type.
Units are only valid for PROFIBUS, local HMI display units
will not be changed.
Select object properties and then Parameter assignment.
Example is shown for Mass totalizer
2.10 Acyclic communication
Acyclic Addressing
Each parameter in a PROFIBUS slave is mapped to an address specified by slot and index.
The slot number refers to an array of data. The index tells you where in the array the data you
want starts.
Acyclic data
Slot Index Range Block
0 16…68 Physical block
1 16…37 Analog input block - Mass flow
68…138 Transducer block
2 16…37 Analog input block - Density
3 16…37 Analog input block - Medium Temperature
4 16…32 Totalizer block 1
5 16…32 Totalizer block 2
6 16…37 Analog input block - Volume Flow
7 16…37 Fraction Flow A block (Manufacturer Specific)
8 16…37 Fraction Flow B block (Manufacturer Specific)
9 16…37 Fraction Flow % A block (Manufacturer Specific)
10 16…37 Fraction Flow % B block (Manufacturer Specific)
11 16…37 Analog input block - Standard volume flow
12 16…37 Analog input block - Frame temperature
13 16…32 Totalizer block 3
14 16…19 Binary commands (Manufacturer Specific)
15 16…33 Dosing block (Manufacturer Specific)
30…255 Used for direct access of MODBUS registers.
Communication
2.10 Acyclic communication
FCT030 Profibus (From firmware 4.0)
26 Function Manual, 06/2018, A5E39931906-AB