Table 2-4 SLOT 0, Physical Block
Index Parameter name Data type
[size]
Access Annotation
16 BLOCK_OBJECT DS-32 Read only Constant block information
17 CURRENT_MODE Unsigned8 Read
only
Follows the target mode
8: Automatic
128: Out of service
22 TARGET_MODE Unsigned8 Read /
write
Desired device mode that is taken over by the CURRENT‐
MODE parameter:
Coding:
8: Automatic
128: Out of service, sets all function blocks into out of service
23 OrderID Visible‐
String(20)
Read only Order ID no.
24 Software_Revision Visible‐
String(16)
Read only String representation of the product firmware version
25 Hardware_Revision Visible‐
String(16)
Read only String representation of the product hardware version
26 VendorID Unsigned16 Read only Unsigned16 identifier of the product manufacturer
27 DEVICE_ID VisibleString
(16)
Read only Product name
28 IM_Serial_Number Visible‐
String(16)
Read only Serial number
29 DIAGNOSIS OctetString(4) Read only Device global alarm information
Byte 0: Bits 0…7 reserved
Byte 1: Bits 0…2 reserved
Bit 3 warm start (restart)
Bit 4 cold start (application reset)
Bit 5 maintenance required
Bits 6…7 reserved
Byte 2: Bit 0 maintenance alarm
Bit 1 maintenance demanded
Bit 2 function check
Bit 3 invalid process conditions
Bit 4 update event
Bits 5…7 reserved
Byte 3: Bits 0…6 reserved
Bit 7 more information is available
31 IM_Tag_Location Visible‐