EasyManua.ls Logo

Siemens Sitrans F Series - Page 17

Siemens Sitrans F Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Slot Module Description
Input (from device to
master)
Output (from master to device)
4 Totalizer 1 - selectable modules
Mass flow totalized:
Mass total Byte 0....3
Byte 4
Mass total (float 32)
Mass total status
-
Mass total set Byte 0....3
Byte 4
Mass total (float 32)
Mass total status
Byte 0
1: Reset
2: Preset
3: Hold
4: Totalize
Mass total (high res) Byte 0....7
Byte 8
Mass total (float 64)
Mass total status
-
Mass total set (high res) Byte 0....7
Byte 8
Mass total (float 64)
Mass total status
Byte 0
1: Reset
2: Preset
3: Hold
4: Totalize
Volumen flow totalized:
Volumen total Byte 0....3
Byte 4
Volumen total (float 32)
Volumen total status
-
Volumen total set Byte 0....3
Byte 4
Volumen total (float 32)
Volumen total status
Byte 0
1: Reset
2: Preset
3: Hold
4: Totalize
Volumen total (high res) Byte 0....7
Byte 8
Volumen total (float 64)
Volumen total status
-
Volumen total set (high
res)
Byte 0....7
Byte 8
Volumen total (float 64)
Volumen total status
Byte 0
1: Reset
2: Preset
3: Hold
4: Totalize
Standard volume totalized:
Standard volumen total Byte 0....3
Byte 4
Standard volumen total
(float 32)
Standard volumen total
status
-
Standard volumen total
set
Byte 0....3
Byte 4
Standard volumen total
(float 32)
Standard volumen total
status
Byte 0
1: Reset
2: Preset
3: Hold
4: Totalize
Standard volumen total
(high res)
Byte 0....7
Byte 8
Standard volumen total
(float 64)
Standard volumen total
status
-
Communication
2.9 Cyclic data exchange
FCT030 Profibus (From firmware 4.0)
Function Manual, 06/2018, A5E39931906-AB 17

Other manuals for Siemens Sitrans F Series

Related product manuals