Slot Module Description
Input (from device to
master)
Output (from master to device)
15
Dosing
Digital dosing Byte 0…3 Amount done
Byte 0
1: Start batch
2: Stop batch
3: Pause batch
4: Resume batch
5: Start cleaning
Byte 4 Amount done status
Byte 5 Dosing state:
0: batch stopped
1: batch running
2: batch paused
Byte 6 Digital output 1
0: close valve 1
1: open valve 1
Byte 7 Digital output 1 status
Byte 8 Digital output 2
0: close valve 2
1: open valve 2
Byte 9 Digital output 2 status
Analog dosing Byte 0…3 Amount done
Byte 0
1: Start batch
2: Stop batch
3: Pause batch
4: Resume batch
5: Start cleaning
Byte 4 Amount done status
Byte 5 Dosing state:
0: batch stopped
1: batch running
2: batch paused
Byte 6…9 Analog output (4… 20
mA)
Byte 10 Analog output status
Process values - 32 bit floating point format
Process values in slot 1, 2, 3, 6, 7, 8, 9, 10, 11 and 12 are represented with the first four bytes
as floating point numbers, according to the IEEE 754 standard. Each value is followed by a
status.
Process value 32 bit Status code
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Totalizers – 32 and 64 bit floating point format
Totalizers in slot 4,5, and 13 can be represented in either 32 bit eg.
Mass total
or
64 bit Mass
total (high res)
.
32 bit totalizers:
Communication
2.9 Cyclic data exchange
FCT030 Profibus (From firmware 4.0)
20 Function Manual, 06/2018, A5E39931906-AB