4.2 Determining a location
Note
The sensor must always be completely filled with liquid.
Figure 4-1 Correct installation with filled pipes
● Avoid the following installations
–
Installation at the highest point in the pipe system
– Installation in vertical pipes with free outlet
Figure 4-2 Wrong installation at high point
Figure 4-3 Correct installation at low point before outlet
Inlet and outlet conditions
To
achieve accurate flow measurement it is essential to have straight lengths of inlet and outlet
pipes and a certain distance to pumps and valves.
It is also important to centre the flowmeter in relation to pipe flanges and gaskets.
Installing/Mounting
4.2 Determining a location
20