SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
30 A5E03434626-04, 05/2015
Danger of poisoning when the device is vented.
If toxic process media are measured with this device, toxic liquids can escape when the device is vented.
•
Before venting, make sure there is no liquid in the device or take the necessary safety precautions.
To commission the pressure transmitter for liquids, proceed as follows:
1. Open both the shut-off valves ⑥ at the pressure tapping point.
2. Open the stabilizing valve
②.
3. With a
pressure transmitter below the differential pressure transducer
, open both blowout valves ⑦ one after the other
until the air-free liquid escapes.
In the case of a
pressure transmitter above the differential pressure transducer
, open both vent valves ⑩ one after the
other until the air-free liquid escapes.
4. Close both drain valves
⑦ or vent valves ⑩.
5. Open the differential pressure valve
③ and the vent valve on the positive side of the pressure transmitter ① slightly,
until fluid escapes without bubbles.
6. Close the vent valve.
7. Open the vent valve on the negative side of the pressure transmitter
① slightly, until fluid escapes without bubbles.
8. Close the differential pressure valve
③.
9. Open the differential pressure valve
④ until the liquid emerges and then close it.
10. Close the vent valve on the negative side of the pressure transmitter
①.
11. Open the differential pressure valve
③ by rotating it in ½ turn.
12. Check and, if necessary, correct the zero point (4 mA) when the start-of-scale value is 0 kPa.
13. Close the stabilizing valve
②.
14. Open the differential pressure valves (
③ and ④) completely.