SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434626-04, 05/2015
31
5.4.4
Commissioning with vapor
Pressure transmitter
Drain valves
Stabilizing valve
Condensate pots
,
Differential pressure valves
Differential pressure transducer/Orifice plate
Differential pressure lines
Insulation
Shut-off valves
Figure 5-2 Measuring steam
Requirement
All valves are closed.
Procedure
WARNING
Hot vapor
Danger of injury or damage to device.
If the shut-off valves
and the differential pressure valve are both open and the stabilizing valve is then opened,
the pressure transmitter
can be damaged by the flow of vapor.
Follow the specified procedure for commissioning.
WARNING
Hot vapor
Danger of injury.
You can briefly open the drain valves
to clean the line. Hot vapor can escape in the process.
Only open the drain valves
briefly, and close them again before vapor escapes.