SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
44 A5E03434626-04, 05/2015
PROFIBUS PA and FOUNDATION
Fieldbus
Output signal 4 … 20 mA Digital PROFIBUS PA or
TM
• Low saturation limit (fully
3.55 mA, set to 3.84 mA in the factory –
•
High saturation limit (fully
adjustable)
23 mA, set to 20.5 mA or optionally
–
• Ripple (without HART
I
SS
≤ 0.5 % of the max. output current –
adjustable time constants
0 … 100 s, continuously adjustable 0 … 100 s, continuously adjustable
Adjustable time constants (T63)
0 … 100 s, in steps of 0.1 s
0 … 100 s, in steps of 0.1 s
•
•
•
Without HART communication
–
H
• With HART communication
HART communicator (Handheld)
Characteristic curve
•
Linearly increasing or linearly decreasing
• Linear increase or decrease or root extraction increase (only for differential
Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)
•
Observe the temperature class in hazardous areas.
Measuring cell with silicone oil
-40 … +85 °C (-40 … +185 °F)
Measuring cell with inert liquid
-20 … +85 °C (-4 … +185 °F)
Measuring cell with inert filling
liquid for relative pressure
measuring cells 1, 4, 16 and 63
-40 ... +85°C (-40...+185°F)
-30 … +85 °C (-22 … +185 °F)
-50 … +85 °C (-58 … +185 °F)
•
Condensation Permitted