SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434626-04, 05/2015
29
All shut-off valves are closed.
To commission the pressure transmitter for gases, proceed as follows:
1. Open both the shut-off valves ⑥ at the pressure tapping point.
2. Open the stabilizing valve
②.
3. Open the differential pressure valve (
③ or ④).
4. Check and, if necessary, correct the zero point when the start-of-scale value is 0 kPa (4 mA).
5. Close the stabilizing valve
②.
6. Open the other differential pressure valve (
③ or ④).