SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
32 A5E03434626-04, 05/2015
To commission the pressure transmitter for vapor, proceed as follows:
1. Open both the shut-off valves at the pressure tapping point.
2. Open the stabilizing valve
.
3. Wait until the steam in the differential pressure lines
and in the equalizing vessels has condensed.
4. Open the differential pressure valve
and the vent valve on the positive side of the pressure transmitter slightly,
until air-free condensate escapes.
5. Close the vent valve.
6. Open the vent valve on the negative side of the pressure transmitter
slightly, until condensate escapes without
bubbles.
7. Close the differential pressure valve
.
8. Open the differential pressure valve
slightly, until condensate escapes without bubbles, then close it.
9. Close the vent valve on the negative side
.
10. Open the differential pressure valve
by rotating it in ½ turn.
11. Check and correct, if necessary, the zero point (4 mA) when the start of scale value is 0 kPa.
The result is only error-free if the differential pressure lines
have equally high condensate columns with the same
temperature. The zero calibration must be repeated if required if these conditions are fulfilled.
12. Close the stabilizing valve
.
13. Fully open the differential pressure valves
and .
14. You can briefly open the drain valves
to clean the line.
15. Close the drain valve
before vapor escapes.
6
Servicing and maintenance
6.1
Basic safety instructions
WARNING
Impermissible repair of explosion protected devices
Danger of explosion in areas subject to explosion hazard.
Repair must be carried out by Siemens authorized personnel only.
WARNING
Impermissible accessories and spare parts
Danger of explosion in areas subject to explosion hazard.
Only use original accessories or original spare parts.
Observe all relevant installation and safety instructions described in the instructions for the device or enclosed with the
accessory or spare part.
WARNING
Maintenance during continued operation in a hazardous area
There is a danger of explosion when carrying out repairs and maintenance on the device in a hazardous area.
Isolate the device from power.
- or -
Ensure that the atmosphere is explosion-free (hot work permit).