Note the e󹪜ect of the ambient temperature on the measuring accuracy in the
section Technical data (Page 61).
For remote seal mounting, observe the notes in the section "Mounting with remote seal" of
the operating instructions.
Mounting location
Verify that the mounting location meets the following conditions:
Accessible
Close to the measuring point
Vibration-free
Within the permitted ambient temperature values
Protect the pressure transmitter from:
Direct heat radiation
Rapid temperature 󹪞uctuations
Heavy contamination
Mechanical damage
Direct sunlight
Note
Select the height of the mounting 󹪞ange such that the pressure transmitter is always mounted
below the lowest 󹪝ll height to be measured.
Procedure
1. Attach the seal to the container's mating 󹪞ange.
Ensure that the seal is centrally positioned and that it does not restrict the movement of the
󹪞ange's seal diaphragm in any way. Otherwise, the seal of the process connection is not
guaranteed to be tight.
2. Screw on the pressure transmitter's 󹪞ange.
3. Observe the installation position.
Installing/mounting
4.4 Installation (level)
SITRANS P320/P420
Compact Operating Instructions, 01/2021, A5E38874562-AC 29

Table of Contents

Other manuals for Siemens SITRANS P