6.3.2 Dierential pressure and ow rate
6.3.2.1 Commissioning in gaseous environments
Requirement
All shut-o valves are closed.
Procedure
$
%
A Pressure transmitter above the dierential
pressure transducer
B Pressure transmitter below the dierential
pressure transducer
① Pressure transmitter ⑦ Blowout valves
② Stabilizing valve ⑧ Condensate vessels (optional)
③,
④
Dierential pressure valves ⑨ Dierential pressure transducer (e.g.
FPS200 and FPS300)
⑤ Dierential pressure lines ⑩ 3-way valve manifold
⑥ Shut-o valves
1. Open both the shut-o valves ⑥ at the pressure tapping point.
2. Open the stabilizing valve ②.
3. Open the dierential pressure valve (③ or ④).
4. Check and, if necessary, correct the zero point when the lower range value is 0 bar (4 mA).
Commissioning
6.3 Application examples
SITRANS P320/P420
48 Compact Operating Instructions, 01/2021, A5E38874562-AC