6.3.2 Di󹪜erential pressure and 󹪞ow rate
6.3.2.1 Commissioning in gaseous environments
Requirement
All shut-o󹪜 valves are closed.
Procedure

$
%
A Pressure transmitter above the di󹪜erential
pressure transducer
B Pressure transmitter below the di󹪜erential
pressure transducer
Pressure transmitter Blowout valves
Stabilizing valve Condensate vessels (optional)
,
Di󹪜erential pressure valves Di󹪜erential pressure transducer (e.g.
FPS200 and FPS300)
Di󹪜erential pressure lines 3-way valve manifold
Shut-o󹪜 valves
1. Open both the shut-o󹪜 valves at the pressure tapping point.
2. Open the stabilizing valve .
3. Open the di󹪜erential pressure valve ( or ).
4. Check and, if necessary, correct the zero point when the lower range value is 0 bar (4 mA).
Commissioning
6.3 Application examples
SITRANS P320/P420
48 Compact Operating Instructions, 01/2021, A5E38874562-AC