Procedure


$
%
A Pressure transmitter below the di󹪜erential pres‐
sure transducer
B Pressure transmitter above the di󹪜erential pres‐
sure transducer
Pressure transmitter Drain valves
Stabilizing valve Gas collector vessels (optional)
, Di󹪜erential pressure valves Di󹪜erential pressure transducer
Di󹪜erential pressure lines Vent valves
Shut-o󹪜 valves 5-way valve manifold
1. Open both the shut-o󹪜 valves at the pressure tapping point.
2. Open the stabilizing valve .
3. With pressure transmitters below the di󹪜erential pressure transducer, partially open
both drain valves one after the other until liquid emerges without bubbles.
In the case of a pressure transmitter above the di󹪜erential pressure transducer, partially
open both vent valves one after the other until liquid emerges without bubbles.
4. Close both drain valves or vent valves .
5. Partially open the di󹪜erential pressure valve and the vent valve (sealing plug with vent
valve) on the positive side of the pressure transmitter until liquid escapes without bubbles.
6. Close the vent valve (sealing plug with vent valve).
7. Partially open the vent valve (sealing plug with vent valve) on the negative side of the
pressure transmitter until liquid escapes without bubbles.
8. Close the di󹪜erential pressure valve .
Commissioning
6.3 Application examples
SITRANS P320/P420
Compact Operating Instructions, 01/2021, A5E38874562-AC 51