Procedure
$
%
A Pressure transmitter below the dierential pres‐
sure transducer
B Pressure transmitter above the dierential pres‐
sure transducer
① Pressure transmitter ⑦ Drain valves
② Stabilizing valve ⑧ Gas collector vessels (optional)
③, ④ Dierential pressure valves ⑨ Dierential pressure transducer
⑤ Dierential pressure lines ⑩ Vent valves
⑥ Shut-o valves ⑪ 5-way valve manifold
1. Open both the shut-o valves ⑥ at the pressure tapping point.
2. Open the stabilizing valve ②.
3. With pressure transmitters below the dierential pressure transducer, partially open
both drain valves ⑦ one after the other until liquid emerges without bubbles.
In the case of a pressure transmitter above the dierential pressure transducer, partially
open both vent valves ⑩ one after the other until liquid emerges without bubbles.
4. Close both drain valves ⑦ or vent valves ⑩.
5. Partially open the dierential pressure valve ③ and the vent valve (sealing plug with vent
valve) on the positive side of the pressure transmitter until liquid escapes without bubbles.
6. Close the vent valve (sealing plug with vent valve).
7. Partially open the vent valve (sealing plug with vent valve) on the negative side of the
pressure transmitter until liquid escapes without bubbles.
8. Close the dierential pressure valve ③.
Commissioning
6.3 Application examples
SITRANS P320/P420
Compact Operating Instructions, 01/2021, A5E38874562-AC 51