6.9.14 Junction System Testing
Using the detect lights on the above ground detectors, ensure that all above ground detectors
(E.g. Kerbside, On-Crossing) are functional and have the required zone of detection.
Using the web page:
Status and Configuration → Controller → I/O → Lines
Or the Handset command “IOP”, check that all road detector loops or other Above Ground
Detector, demand pushbuttons etc are correctly connected/configured.
Clear all faults in the log and allow the junction to run normally. Periodically check the fault table
/ system log and ensure that no faults are raised. Verify that the controller has the correct date
and time and is keeping correct time.