9 – 95
9.2.3.5 Analog output module
Function
With the analog output module, analog measured values can be transmitted, which can be shown on the cubicle door by means
of moving-coil instruments. A total of 4 outputs is available.
For the output signal, two different formats can be selected:
- 4 - 20 mA, output via terminal strip X5
- 0 - 10 V, output via terminal strip X4
Installation
(page 9-83)
Connection
Connection setup (page 9-83)
A maximum of 2 analog output modules can be connected; the rotary coding switches of these modules must, however, have different
settings.
Terminal assignment
Settings
Changing settings (page 9-86)
The measured values to be signaled are adjusted using the rotary switch. They are always present on the two terminal strips in the
corresponding format.
The following values are available at the outputs:
Output assignment
Position AO 1 AO 2 AO 3 AO 4
I I
L1
I
L2
I
L3
I
N
U U
L12
U
L23
U
L31
U
L1N
P P
L1
P
L2
P
L3
S
total
f f U
LLavg
P
total
P. F.
avg
P. F. P. F.
L1
P. F.
L2
P. F.
L3 Phase unbalance current in%