EasyManua.ls Logo

Siemens XC1001-A - Fcp1004-E

Siemens XC1001-A
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overview
15
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
4.4 FCP1004-E
Fig. 4 FCP1004-E power supply unit
Mark Function Remarks
1 Mains voltage setting Shunt ON = 115VCA, shunt OFF = 230VCA
2 Mains terminal block
3 Mains fuse 4A / 250V
4 System start without mains power Shunt the 2 terminals with a jumper and
remove after system start
5 Temperature sensor for battery charging voltage compensation Do not cover
6 Internal green LED «Mains operation» but visible from the front Not lit if no mains voltage
7 Battery connection
8 XCM1002 main board connection
Security level of terminal blocks 1 and 2: Dangerous voltage
Security level of other terminal blocks: SELV (Safety Extra Low Voltage)