Programming
62
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
12.3 Steps 01 to 04 - Time duration settings
Step
O
p
tion
Description
01 Pre-discharged warning time for automatic release (check programming step 65 for manual release)
The Pre-discharged warning time sets the countdown duration before the actuator extinguishing release triggering. During this time,
the reset function is not possible. Adjustable from 0 to 120 seconds by step of 5 seconds
Default : 30 s
Values from 65 seconds to 120 seconds are not compliant to EN12094-1. This must be clearly indicated in the installation test
report. (Application: activation of very slow dampers (100 - 120 seconds to open), during the pre-discharged warning time
00 0 second
05 5 seconds
10 10 seconds
15 15 seconds
20 20 seconds
25 25 seconds
30 30 seconds
35 35 seconds
40 40 seconds
45 45 seconds
50 50 seconds
55 55 seconds
60 60 seconds
61 65 seconds
62 70 seconds
63 75 seconds
64 80 seconds
65 85 seconds
66 90 seconds
67 95 seconds
68 100 seconds
69 105 seconds
70 110 seconds
71 115 seconds
72 120 seconds
02 Monitored output 4 : activation duration
The actuator activation time sets the duration of extinguishing release output to Control Line 4. During this time, the reset function
is not possible.
Adjustable:
- from 5s to 300s (5mn) seconds by step of 5s
- from 5mn30s to 10mn by step of 30s
- from 11mn to 30mn by step of 1mn
- until "Reset" operation
Default: 5 s
Note 1: For pyrotechnical actuators select an activation time of 5s
Note 2: For solenoid actuators, select an activation time of at least 10s. Keep this time duration to a minimum in order to minimize
current consumption
According to EN12094-1 option with requirement 4.21, this duration can be cancelled by using code (operating access level 3). It is
applicable only for installations using electrical valves where the gas concentration is directly function of the valve opening duration.
01 5 seconds
02 10 seconds
03 15 seconds
¦
¦
58 290 seconds
59 295 seconds