Connection to Sinteso / Cerberus PRO panels
90
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
18 Connection to Sinteso / Cerberus PRO panels
The XC10 control panel can be integrated into a Sinteso / Cerberus PRO fire
detection system. This integration offers the possibility to:
- send XC10 status to the fire control panel
- transmit commands from the fire control panel to the XC10
The integration uses IO modules connected to the FDnet (FDCI222 / FDCIO222 /
FDCIO224).
18.1 XC10 zone
Sinteso / Cerberus PRO engineering tool FXS allows the creation of one or several
“XC10 zones” (under “Section” level). Each “XC10 zone” is created with a pre-
configured set of 4 inputs and 3 outputs elements:
An “XC10 zone” can be configured using 5 options check boxes:
- Autom. exting. release blockable from Sinteso / Cerberus PRO panel:
If this option is selected, command “Autom. exting. ON/OFF” is available in the
“XC10 zone / execute commands” menu. When this command is executed, the
“XC10 zone” element 2:Output ‘Block autom.’ is activated and an acknowledge
from XC10 is expected during 5 seconds (line open on FDCIO222 IN4, see
table below). If it’s received in time, the isolation message “Aut.ext.OFF FC” is
displayed. If it is not received in time, the “XC10 zone” element 2:Output ‘Block
autom.’ is automatically de-activated and the information message “XC10 not
blockable” is displayed.
- Autom.+manual exting. release blockable from Sinteso / Cerberus PRO panel:
If this option is selected, command “Autom.+man. exting. ON/OFF” is available
in the “XC10 zone / execute commands” menu. When this command is
executed, the “XC10 zone” element 3:Output ‘Block autom.+manual’ is
activated and an acknowledge from the XC10 is expected during 5 seconds
(short-circuit on FDCIO 222 IN4, see table below). If it’s received in time, the
isolation message “Aut+man ext.OFF FC” is displayed. If it is not received in
time, the “XC10 zone” element 3:Output ‘Block autom.+manual’ is automatically
de-activated and the information message “XC10 not blockable” is displayed.
- Show blocking of autom. Exting. release on Sinteso / Cerberus PRO operating
terminal: