Programming
72
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
03 "Manual blocked"
1) 3)
04 "Automatic and manual blocked"
1) 3)
05 External device disabled
1)
06 "RT-Alarm" and "RT-Fault" disabled
1)
07 External device fault
1)
(“Reset” operation is required to eliminate the fault indication)
08 External power supply fault
1)
09 Fault on "RT-Fault" line from external device remote transmission (transmitter, for example)
1)
10 Level 2 operating access
1) 3)
11 "Silence/Resound" sounders
2) 3)
12 No effect
13 Toggle function between “Automatic blocked” condition and “Normal” condition
2) 3)
Application: for RU only
Not compliant to EN12094-1 chapter 4.23.2 because input is not monitored
50 Non monitored control input 3
Same options as non monitored control input 2 – default = 12
51 Non monitored control input 4
Same options as non monitored control input 2 – default = 12
1)
State is maintained as long as a potential +24V is applied
2)
Pulse control (0.2 s minimum)
3)
Control must be possible through a level 2 access device only
12.14 Steps 52 to 55 - Detection zones
Step
O
p
tion
Description
52 Alarm verification: select zones (*)
01 No alarm verification
02 Zone 1
03 Zone 2
04 Zones 1 and 2
05 Zone 3
06 Zone 1, 2 and 3
(*)The alarm condition is enabled only after 2 consecutive alarms in less than 60 seconds (the 1st one is reset automatically). The
delay for the second alarm is 8 s. If the second alarm doesn’t come within 60 s, the first alarm is automatically reset. The first
alarm is indicated by the red led during 2 s.
53 Automatic release: select zones combination
01 Alarm zone 1 AND Alarm zone 2
02 ( Alarm zone 1 AND Alarm zone 2 ) OR ( Fault zone 1 AND Alarm zone 2 ) OR ( Alarm zone 1 AND Fault zone 2 )
03 Alarm zone 1 AND Alarm zone 2 AND Alarm zone 3
04 ( Alarm zone 1 AND Alarm zone 2) OR Alarm zone 3
05 ( Alarm zone 1 AND Alarm zone 3 ) OR ( Alarm zone 2 AND Alarm zone 3 ) OR ( Alarm zone 1 AND Alarm zone 2 )
06 Alarm zone 1 OR Alarm zone 2
07 Alarm zone 1
Care shall be taken using option 04, 06 and 07 as it triggers the extinguishing process on a single alarm
54 Zones disabling
01 Zone1 .. Zone 4 Disable/Test" is allowed
02 Zone1 .. Zone 4 Disable/Test" is not allowed
03 Zone 4 Disable/Test" is not allowed
04 Zone1 .. Zone 3 Disable/Test" is not allowed
05 Zone1 .. Zone 2 Disable/Test" is not allowed
55 Zone 3 : Fire alarm condition
01 "Fire alarm" condition indicated, RT-Alarm activated
02 "Fire alarm" condition indicated, RT-Alarm not activated