Programming
66
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
13 Active in state “Automatic Blocked”
14 Active in state "Manual blocked”
15 Active in state "Automatic blocked” or "Manual blocked"
16 Active in state "Automatic blocked” and "Manual blocked"
17 Active in state "Emergency hold/abort"
18 Processing as "Sounders", follows the activation of monitored output 1 (see steps 05 and 10 and paragraph 12.1)
19 Active in state "Fire alarm" until “Reset”
20 Active in state "Activated" until “Reset”
21 Active in state "Released" until “Reset”
22 Active in state "Fire alarm" or "Activated" or "Released" until “Reset”
23 Active in state "Activated" or "Released" until “Reset” (same as option 20)
99 Not used (no EOL required)
12.7 Steps 15 to 19 - Relay contact 1 to 5
Description
15 Relay output 1 : select the function
01 Processing as “Fire controls A” (see paragraph 12.1)
02 Processing as “Fire controls B” (see paragraph 12.1)
03 Processing as “Fire controls C” (see paragraph 12.1)
04 Active in state ”Fire alarm” until “Reset”
05 Active in state ”Activated” until “Reset”
06 Active in state ”Released” until “Reset”
07 Active in state “Fire alarm” or “Activated” or ”Released” until “Reset”
08 Active in state “Activated” or ”Released” until “Reset” (same as option 05)
09 Active in state “Loss of agent”
10 Active in state “Detector test”
11 Active in state “Disabled”
12 Active in state “Emergency hold/abort”
13 Active in state “Mechanical blocked”
14 Active in state “Automatic blocked”
15 Active in state “Manual blocked”
16 Active in state “Automatic blocked” or “Manual blocked”
17 Active in state “Automatic blocked” and “Manual blocked”
18 Processing as "RT-alarm"(see step 06 and paragraph 12.1)
19 Processing as "RT-fault"(see step 07 and paragraph 12.1)
20 Inactive in state “Fault” or “Disable” or “Mechanical blocked” or “Loss of agent” or “Incorrect status”
Active in all other states
21 Active during 5 seconds when the key reset is pressed
Application: reset of an XC10 panel and reset of an ASD system within a single operation
22 Active in state:
- “Manual blocked”
- Zone 4 in fault condition
- “Processing as actuator” control lines in fault condition
- Actuator disabled
23 Active in state Zone 1 alarm condition until “Reset”
24 Active in state Zone 2 alarm condition until “Reset”
25 Active in state Zone 3 alarm condition until “Reset”
26 Active in state Zone 4 manual release activated condition until “Reset”
27 Processing as "Extract fan"(see paragraph 12.1)
28 Processing as "Fire damper"(see steps 63 and 64 and paragraph 12.1)
29 Processing as “Door holder” (see paragraph 12.1)