Test functions
86
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
15.7 Individual output test
All the outputs, except those programmed as actuators, can be tested individually:
- Each individual test, once enabled, automatically ends after 1 mn if no action is
carried out for this period
- Outputs can be tested only one by one (duration = 3 mn max.)
During test phase:
- Alarms and faults are not indicated
- Extinguishing process cannot be started
- Programming access is not possible
- Connection with the maintenance PC cannot be enabled
Procedure
1. Remove the front plastic cover (XC1001-A)
2. Enable operating access level 2
3. Press and hold down the key « Silence buzzer » (6), then enter
the code 3 4 2 1 1 2 on the keypad:
è Display indicates « 0101 »
è « System fault » (4), « Earth fault » (5) and « Disable » (6) led light up
alternatively, « Operating access » led (10) goes out
4. Press the key « Silence buzzer » (6) to choose the category of the output to be
tested (represented by both digits on the left of the display):
è 01 = monitored outputs
è 02 = relay outputs
è 03 = driver outputs
5. Press the « Mode select » key (8) to choose the number of the output to be
tested (represented by both digits on the right of the display)
6. Press the « Led test » key (9) to start the test:
è The output is enabled for 3 mn (press the « Led test » (9) key again to disable
it before 3 mn, if necessary)
7. Start operations 4. to 6. again to test another output
8. Press the « Reset » key (7) to leave the test