Programming
68
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
22 Active in state:
- “Manual blocked”
- Zone 4 in fault condition
- “Processing as actuator” control lines in fault condition
- Actuator disabled
23 Active in state Zone 1 alarm condition until “Reset”
24 Active in state Zone 2 alarm condition until “Reset”
25 Active in state Zone 3 alarm condition until “Reset”
26 Active in state Zone 4 manual release activated condition until “Reset
27 Processing as "Extract fan" (see paragraph 12.1)
28 Processing as "Fire damper" (see steps 63 and 64 and paragraph 12.1)
29 Processing as “Door holder” (see paragraph 12.1)
30 Processing as “Sounders(see steps 05 and 10 and paragraph 12.1)
31 Active in state "selector valve opened" (XCA1030 multi-sector module)
32 Active in state "Extinguishing activated from electrical manual release"
33 Active in state "Extinguishing activated from automatic detectors"
34 Active in state "Extinguishing activated from remote activation"
35 Active in state "Fault" condition
36 Active in state of monitored outputs 1 or 2 or 3 activated
37 Active in state of monitored output 4 activated
38 Active in state of monitored output 5 activated
39 Processing as “RT-alarm” (like on step 15 option 18)
40 Processing as “RT-fault” (like on step 15 option 19)
41 Active in state of selector valve is blocked (in case of a multi sector system and an other sector is activated)
42 Active in case of LED test is pressed during x seconds
43 Processing as “Door holder” inverted
99 Not used
21 Driver output 2 : select the function
Same options as unmonitored output 1 – default = 07
22 Driver output 3 : select the function
Same options as unmonitored output 1 – default = 05
23 Driver output 4 : select the function
Same options as unmonitored output 1 – default = 06
24 Driver output 5 : select the function
Same options as unmonitored output 1 – default = 11
25 Driver output 6 : select the function
Same options as unmonitored output 1 – default = 15
26 Driver output 7 : select the function
Same options as unmonitored output 1 – default = 12
27 Driver output 8 : select the function
Same options as unmonitored output 1 – default = 13
12.9 Steps 28 to 31 - Monitored inputs 1 to 4
Step
O
p
tion
Description
28 Monitored input 1 : released contact
01 Contact (1.2 kΩ) normally closed when there is no gas in piping
02 Contact (1.2 kΩ) normally opened when there is no gas in piping
03 No contact, "Released" condition will be indicated as soon as actuators are activated (EOL resistor not required)
29 Monitored input 2 : loss of agent contact
01 Contact (1.2 kΩ) normally closed when cylinders pressure/weight is correct