Description
05 Sounders: program the pattern
Fire alarm Activated Emergency hold/abort Released
01 Continuous Pulsated fast Pulsated slow Pulsated fast
02 Pulsated slow Pulsated fast Pulsated slow Continuous
03 Pulsated fast Pulsated long Pulsated fast Continuous
04 Pulsated slow Continuous Pulsated slow Continuous
05 Continuous Continuous Pulsated slow Pulsated fast
06 Continuous Continuous Continuous Continuous
07 Pulsated slow Continuous Continuous Continuous
08 Not activated Continuous Pulsated slow Continuous
09 Pulsated long Pulsated fast Pulsated slow Continuous
10 Pulsated fast Continuous Continuous Continuous
11 Pulsating fast Continuous Pulsating fast Continuous
12 Not activated Pulsated fast Not activated Continuous
Pulsated fast = Active 1 second / Inactive 1 second
Pulsated slow = Active 1 second / Inactive 4 seconds
Pulsated long = Active 4 seconds / Inactive 1 second
Note: according to EN 12094-1 paragraph 4.30.2, sounders activation during released condition shall be continuous
12.5 Steps 06 to 09 - Remote transmission
Description
06 RT-alarm: program the activation
01 Active in state fire alarm until "Reset"
02 Active in state fire alarm, activated, released until "Reset"
03 Active in state activated, released until "reset"
04 Active in state released until "reset"
05 Active in state fire alarm, activated, released, zone 4 in alarm condition, until "reste"
Application: transmit RT-Alarm as soon as the DM1103-L is activated, even if “Manual blocked” is selected
07
RT-fault : program the activation
01 Activation : without delay on any fault
Duration : until buzzer silence
02 Activation : without delay on any fault
Duration : until buzzer silence and fault elimination
03 Activation : after 3 mn, on any fault, if buzzer is not silenced
Duration : until buzzer silence
04 Activation : after 3 mn, on any fault, if buzzer is not silenced
Duration : until buzzer silence and fault elimination
05 Activation : without delay on any fault, disable, mechanical blocking, loss of agent, incorrect status
Duration : until activation cause disappears
08 « Remote transmission » LED (9): activation and operation
01 Lights up on RT-alarm (Enable/Disable, via key 11, possible)
02 Lights up on RT-alarm and RT-fault (Enable/Disable, via key 11, possible)
03 Unused (key 11 disabled)
Application: Remote transmission not used [FR]
à
outputs programmed as “ Remote transmission” cannot be disabled
04 Lights up on Control Output 1 or 2 or 3 activated
Application: for Austria only
09 RT-Alarm and RT-Fault suppression when operating access level 2
01 Remote transmission not blocked