Programming
73
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
12.15 Steps 56 to 57 - Operating access level
Step
O
p
tion
Description
56 "Silence buzzer": change access level
01 Possible at access levels 1 and 2
02 Possible at access level 2 only
57 Access level 2
01 Default code = 4 2 3 3
02 Individual access code:
1. Enter the desired code on the keyboard (4 to 6 digits)
2. Press the key (12) "Disable / Test zone 1" :
è red led zone 1 (25) flashes
3. Repeat operations 1 and 2 (code confirmation) :
è red led zone 1 (25) lights continuously = code accepted
è yellow led zone 1 (26) flashes
= code not accepted (repeat operations 1 to 3)
03 Operating access level 2 is provided with an external optional key (in this case, code access is not possible)
12.16 Step 58 - Multi-sector
Step
O
p
tion
Description
58 Multi-sector operation
01 The panel is not part of a multi-sector installation
02 The panel is part of a multi-sector installation, including inter-blocking (see EN12094-1 option 4.29) / Valid only for XC1003-A
03 The panel is part of a multi-sector installation, without inter-blocking / Valid only for XC1003-A
04 Same as option 02 but actuators lines 1 and 2 from XCA1031 are de-activated in case of "Emergency Hold/Abort" during the
pre-discharged warning time.
Application: for Austria only
12.17 Step 59 - Detector type
Step
O
p
tion
Description
59 Detector type
01 Detectors without current limitation (Algorex / Sinteso)
02 Detectors with current limitation (Synova)
03 Detectors without current limitation (Algorex / Sinteso) BS5839Pt1 compliant
04 Detectors with current limitation (Synova) BS5839Pt1 compliant
12.18 Steps 60 to 61 - Repeaters
Step
O
p
tion
Description
60 Repeaters: configure the number of repeaters connected on the RTNet
00 No repeaters
01 1
02 2
03 3
04 4
05 5
06 6