Programming
63
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
60 300 seconds (5mn)
61 5mn 30s
62 6mn
63 6mn 30s
64 7mn
65 7mn 30s
66 8mn
67 8mn 30s
68 9mn
69 9mn 30s
70 10mn
71 11mn
72 12mn
73 13mn
74 14mn
75 15mn
76 16mn
77 17mn
78 18mn
79 19mn
80 20mn
81 21mn
82 22mn
83 23mn
84 24mn
85 25mn
86 26mn
87 27mn
88 28mn
89 29mn
90 30mn
99 Until "Reset"
03 Monitored output 5 : activation duration
Applicable, with the same options as at step 02, only if this output is set to “Process as actuator” (see step 14).
04 Flooding time
The flooding time sets the duration the gas concentration must be maintained. During this time, the reset function is not possible.
Adjustable from 0 to 30 minutes by step of 1 minute
Default: 1 minute
00 30 seconds
01 1 minute
02 2 minutes
03 3 minutes
¦
¦
28 28 minutes
29 29 minutes
30 30 minutes