EasyManua.ls Logo

Sime FORMAT DGT 30e - Air;Combustion Products Divider; Outlet Systems; Positioning the Outlet Terminals

Sime FORMAT DGT 30e
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
6.2.8 POSITIONING THE
OUTLET TERMINALS
The outlet terminals for forced-draught
appliancesmay belocatedin theexter-
nalperimeterwallsofthebuilding.
To provide some indications of possible
solutions,tobeobserved,withreference
to the type of building shown in fig. 14
and14/a,givestheminimumdistances.
6.2.7.1 Air/combustion
products divider
The air/combustion products divider
cod.8093020 (fig. 12) is supplied with a
diaphragm,segmentsmustberemoved,
depending on the maximum head loss
accepted in both ducts, as indicated in
fig.12/a.
6.2.7.2 Outlet systems
Thediagramsinfig.13illustrateanum-
ber of examples of different types of
separateoutlets.
No. segments Total load loss
to remove mm H2O Pa
none 0÷0.8 0÷7.85
No.1 0.8÷1.5 7.85÷14.7
No.1e2 1.5÷2.4 14.7÷23.5
fromNo.1to3 2.4÷3.2 23.5÷31.4
fromNo.1to4 3.2÷4.0 31.4÷39.2
fromNo.1to5 4.0÷4.8 39.2÷47.1
fromNo.1to6 4.8÷5.6 47.1÷54.9
fromNo.1to7 5.6÷6.5 54.9÷63.7
fromNo.1to8 6.5÷7.3 63.7÷71.6
fromNo.1to9 7.3÷7.8 71.6÷76.5
fromNo.1to10 7.8÷8.4 76.5÷82.4
withoutdiaphragm 8.4÷9.5 82.4÷93.2
1
2
3
4
L
K
1 2 0
190
190
ø 80
ø 80
125
125
Fig.12
KEY
1 Divider with vent
2 Inlet air diaphragm
3 Air intake bend
4 Exhaust bend
30
K mm 221
L mm 450
Fig.12/a

Table of Contents

Other manuals for Sime FORMAT DGT 30e

Related product manuals