EasyManuals Logo

Sime FORMAT DGT 30e User Manual

Sime FORMAT DGT 30e
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
21
6.2.8 POSITIONING THE
OUTLET TERMINALS
The outlet terminals for forced-draught
appliancesmay belocatedin theexter-
nalperimeterwallsofthebuilding.
To provide some indications of possible
solutions,tobeobserved,withreference
to the type of building shown in fig. 14
and14/a,givestheminimumdistances.
6.2.7.1 Air/combustion
products divider
The air/combustion products divider
cod.8093020 (fig. 12) is supplied with a
diaphragm,segmentsmustberemoved,
depending on the maximum head loss
accepted in both ducts, as indicated in
fig.12/a.
6.2.7.2 Outlet systems
Thediagramsinfig.13illustrateanum-
ber of examples of different types of
separateoutlets.
No. segments Total load loss
to remove mm H2O Pa
none 0÷0.8 0÷7.85
No.1 0.8÷1.5 7.85÷14.7
No.1e2 1.5÷2.4 14.7÷23.5
fromNo.1to3 2.4÷3.2 23.5÷31.4
fromNo.1to4 3.2÷4.0 31.4÷39.2
fromNo.1to5 4.0÷4.8 39.2÷47.1
fromNo.1to6 4.8÷5.6 47.1÷54.9
fromNo.1to7 5.6÷6.5 54.9÷63.7
fromNo.1to8 6.5÷7.3 63.7÷71.6
fromNo.1to9 7.3÷7.8 71.6÷76.5
fromNo.1to10 7.8÷8.4 76.5÷82.4
withoutdiaphragm 8.4÷9.5 82.4÷93.2
1
2
3
4
L
K
1 2 0
190
190
ø 80
ø 80
125
125
Fig.12
KEY
1 Divider with vent
2 Inlet air diaphragm
3 Air intake bend
4 Exhaust bend
30
K mm 221
L mm 450
Fig.12/a

Table of Contents

Other manuals for Sime FORMAT DGT 30e

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sime FORMAT DGT 30e and is the answer not in the manual?

Sime FORMAT DGT 30e Specifications

General IconGeneral
BrandSime
ModelFORMAT DGT 30e
CategoryBoiler
LanguageEnglish

Related product manuals