EasyManua.ls Logo

Sime FORMAT DGT 30e - Dismantling the Casing; General Boiler Maintenance; Ignition;Detection Electrode Maintenance

Sime FORMAT DGT 30e
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
press
1
2
3
4
until
appears.
Confirmthisvalueusing
1
2
3
4
or
1
2
3
4
.
Exittheparameterssectionby pressing
1
2
3
4
.
The table below gives the values to set
whenthesupplygasischanged:
6.4.2.2 Adjusting valve pressure
(fig. 24)
Setmaximumandminimumpressureon
gasvalvesasfollows(fig.24):
– Connect a manometer to the intake
downstream of the gas valve (4 fig.
22).
Disconnect the valve VENT pressure
test point tube (5 fig. 22).
– Removethecap(1)fromthemodula-
tor.
- Puttheboilerinchimneysweepmode
(see section 6.4.4.2), ensure that ane
zonevalvesareopen.
– Pressthekey
1
2
3
4
(Hi).
- Turning the gas valve adjusters
clockwisewilldecreaseit.
- Adjust maximum pressure using the
nut(3)withawrenchtothemaximum
pressure valve indicated in Table 4
(fig.22).
– Adjust themaximumpressure before
adjustingtheminimum.
– Pressthekey
1
2
3
4
(Lo).
– Hold the nut (3) in place, turn the
screw (2) to the minimum pressure
indicatedinTable 4.
– Alternatelypressthekeys
1
2
3
4
and
1
2
3
4
and check that the maxi-
mumandminimum pressures corre-
spond to the set values; if necessary
readjust.
– Pressthekey
1
2
3
4
againtoquitthefun-
ction.
– RefitthevalveVENTpipe.
– Remove the manometer, remembe-
ring to tighten the screw for closing
thepressuretestpoint.
– Put the plastic cap (1) back on the
modulator. Check all test points and
connectionsforgastightness.
6.4.3 DISMANTLING
THE CASING (fig. 25)
The casing may be removed complete-
ly to facilitate boiler maintenance, as
showninfig. 25.Turn thepanel control
forwardforaccess totheinternal com-
ponentsoftheboiler.
6.4.4 MAINTENANCE
To guarantee functioning and efficien-
cy of the appliance, in respect of the
legal provisions in force, it must be
regularly checked; the frequency of the
checks depends on the type of instal-
lation and usage but this should be at
least annually.
Carry out the following procedure for
cleaningtheburner/heatexanger:
– Isolate the boilers electrical supply
andclosethegasisolationvalve.
– Removethe outercasingasshownin
fig.25;removethecombustioncham-
bercoverandtheburnercover.
– Idealyuseavacuumcleanerandasoft
brushtoremoveanydebris;takecare
nottodamagetheinsulationpanel.
- Clean the heat exchanger, removing
anydustorresiduefromcombustion.
- Whencleaning theheat exchangeror
theburner,chemicalproductsorsteel
brushesMUSTNOTBEUSED.
6.4.4.1 Ignition/Detection
electrode (fig. 27)
- Remove the casing, front panel and
sealedchambercovers.
- Unscrewthescrewsecuringtheelec-
trodeandremovefromtheburner.
- disconnecttheelectrodecable.
- Replacetheelectrodeandsetthegap
asshown.
3
2
1
Fig.24
KEY
1 Plastictap
2 Minimumpressureadjustingnut
3 Maximum pressure adjusting
nut
BOILER GAS MODELS PAR 1
METHANE 30 02
 30 i
 
30 e
LPG 30 04
1
2
4 x
Fig.25
Codice/Code 8109292
Modello/Model FORMAT DGT 30 i
Matricola/Serial n. 9999999999
PAR 1 = 02 (NG)/ 04 (LPG)
PAR 2 = 09
1
2
3
4
IGNITION/DETECTION
ELECTRODE
4±0,5
Fig.27

Table of Contents

Other manuals for Sime FORMAT DGT 30e

Related product manuals