6.3.2 ACCESS TO INSTALLER’S
PARAMETERS
To access the installer parameters,
press simultaneously the keys of boiler
panel
1
2
3
4
and
1
2
3
4
for5seconds.
The red LED flashes and the display
shows:
Theparameterscanbescrolledwith
1
2
3
4
or
1
2
3
4
. To enter the parameter press
or
1
2
3
4
.Thevaluesetflashes,thedisplay
shows:
Proceed as follows to change the set
value:
– setthenewvalueusing
1
2
3
4
or
1
2
3
4
.
–
confirmthesetvalueusing
1
2
3
4
or
1
2
3
4
.
Press
1
2
3
4
to exitthe parameters section.
Thedisplayisshownautomaticallyafter
5minutes.
The parameters section contains the
alarms log, info and meters (display
only).
6.3.2.1 Replacing the board or
RESETTING parameters
If the electronic board is replaced or
reset,itisnecessarytoconfigurePAR01
andPAR02byassociatingthefollowing
valuestoeachtypeofboilertobeableto
restarttheboiler:
NOTE: the boiler panel has a label with
the values that have to be set for PAR 01
and PAR 02 (fig. 25).
1
2
3
4
1
2
3
4
BOILER GAS MODELS PAR 1
METHANE 01
FORMAT (G20) 30 02
DGT LPG 03
(G30/G31)
30 04
PARAMETERS INSTALLER
FAST CONFIGURATION
PAR DESCRIPTION RANGE UNITOF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
01 Combustionconfiguration --=ND = = “--”
1...8
02 Hydraulicconfiguration --=ND = = “--”
1...22
03 IlluminationofthegreenLED 0=Disabled = = 01
1=Enabled
04 Correctionofexternalprobevalues -5...05 °C 1 00
05 Timerblockofthekeys --=Disabled Min. 1 15
 1...99
D.H.W. - HEATING
PAR DESCRIPTION RANGE UNITOF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
10 Boilerantifreeze 0...10 °C 1 03
11 Externalsensorantifreeze --=Disabled °C 1 -2
-9...05
12 Climaticcurvesetting 03...40 = 1 20
13 Minimumtemperatureheating 40...PAR14 °C 1 40
14 Maximumtemperatureheating PAR13...80 °C 1 80
15 Maximumpowerheating 30...99 % 1 99
16 Post-circulationtime 0...99 10sec. 1 03
17 Pumpheatingactivationdelay 0...99 10sec. 1 01
18 Re-ignitiondelay 0...10 Min. 1 03
19 ModulationD.H.W.flowmeter --=Disabled = = 01
1=Enabled
29 Anti-legionella(onlyD.H.W.tank) --=Disabled °C 1 “--”
 50...80
PARAMETERS RE-SET
PAR DESCRIPTION RANGE UNITOF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
49* Resetdefaultparameters --,1 = = =
(PAR01-PAR02equal“---”)
* Should the boiler operate in an erratic manner, it is advisable to reset to “factory settings” by PAR 49 = 1
and PAR 1 and PAR 2 as specified in point 3.2.1.
ALARMS (visualization)
PAR DESCRIPTION RANGE UNITOF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
A0 Codeoflasterror = = = =
A1 Codeoflasterror-1 = = = =
A2 Codeoflasterror-2 = = = =
A3 Codeoflasterror-3 = = = =
A4 Codeoflasterror-4 = = = =
A5 Codeoflasterror-5 = = = =
A6 Codeoflasterror-6 = = = =
A7 Codeoflasterror-7 = = = =
A8 Codeoflasterror-8 = = = =
A9 Codeoflasterror-9 = = = =
INFO (visualization)
PAR DESCRIPTION RANGE UNITOF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
i0 Externalsensortemperature -9...99 °C 1 =
i1 C.H.1sensortemperature -9...99 °C 1 =
i2 C.H.2sensortemperature -9...99 °C 1 =
i3 D.H.W.sensortemperature -9...99 °C 1 =
i4 AuxiliarysensorAUXtemperature -9...99 °C 1 =
i5 Setofeffectiveheatingtemperature PAR13...PAR14 °C 1 =
i6 Levelsurveyflame 00...99 % 1 =
i7 Currenttothemodulator 00...17 10mA 1 =
i8 FlowrateD.H.W.flowmeter 00...99 l/min 1 =
COUNTERS (visualization)
PAR DESCRIPTION RANGE UNITOF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
c0 Numberhoursofoperationoftheburner 00...99 hx100
0,1from0,0to9,9
00

1from10to99
c1 Numberofignitionsoftheburner 00...99 x1000
0,1from0,0to9,9
00

1from10to99
c2 Numbertotaloftheerrors 00...99 x1 1 00
c3
Numberoftimetheinstallerparametersaccessed
00...99 x1 1 00
c4
OftimetheOEMparametershavebeenaccessed
00...99 x1 1 00
1
2
3
4
BOILER PAR 2
FORMAT DGT combined 09
FORMAT DGT 10
combined
with sun-panel system
FORMAT DGT SYSTEM 12
FORMAT DGT 14
combined
with sun-panel system
and with automatic filling