EasyManua.ls Logo

Sime FORMAT DGT 30e - Chimney Sweep Function

Sime FORMAT DGT 30e
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
6.4.4.2 Chimney sweep
function
Tocheckboilercombustion,pressatthe
sametimetheinstaller’skey(
1
2
3
4
e
1
2
3
4
)
forafewseconds.
Thechimneysweep function willswitch
onandwillcontinuefor15minutes.
During the 15 minutes functioning of
chimney sweep function, pressing the
keys(
1
2
3
4
and
1
2
3
4
)taketheboilerrespec-
tive at maximum (Hi) and at minimum
(Lo)power.
From thatmoment,the boiler will start
working in heating mode at maximum
power,withcut off at80°C and re-igni-
tionat70°C.
Before activating the chimney sweep
function make sure that the radiator
valves or eventual zone valves are
open.
Thetestcanalsobecarriedoutwiththe
boilerworkinginD.H.W.mode.
For this, after activating the chimney
sweep function, open one or more hot
waterfaucets.
Under these conditions, the boiler will
function at maximum power with the
D.H.W.keptatbetween60°Cand50°C.
During the test, the hot water faucets
mustremainopen.
For exit to the chimney sweep function
pressthekey
1
2
3
4
ofthecontrolpanel.
The chimney sweep function will auto-
matically switch off after 15 minutes
from the activation.
6.4.5 ERROR MESSAGES
When there is a ERROR message, an
alarm appears on the display and the
RED LED will illuminate.
DescriptionsoftheERRORSwithrelative
alarmsandsolutionsaregivenbelow:
In the case of repeated shutdown of this
appliance, take appropriated action to
find the cause and remedy the problem.
– FUMES DISCHARGE ERROR
ALARM 01 (fig.4)
ThedisplayshowsAL01Itcanbecau-
sedby:
a)Thefanisfaultyorjammed.
b)Theairpressureswitchhasinter-
venedorisfaulty.
– LOW WATER PRESSURE ERROR
ALARM 02 (fig.4/a)
Ifthe pressuredetected by thewater
pressure valve is lower than 0.5 bar,
theboilerstopsandthedisplayshows
thealarm “AL02”.Repressurise the
heatingsystembyuseoftheexternal
fillingloop.
Until the pressure indicated on the
hydrometerreaches1 - 1.2 bar.
WHEN FILLING HAS BEEN COMPLE-
TED,ENSURETHATTHEFILLINGDE-
VICEISTURNEDOFF.
If the filling procedure has to be re-
peated several times, it is advisable
to check the heating circuit is intact
(check that there are no leaks).
– D.H.W. SENSOR ERROR
ALARM 04
The D.H.W. probe is not operational
in these boiler models; if the display
showstheAL 04anomaly,checkPAR
2.
– HEATING SENSOR ERROR
ALARM 05
If one or both sensing elements of
heating sensor (SM1/SM2) are open
or short circuited, the boiler will not
functionandthedisplaywillshowthe
alarm“AL05”.
– FLAME LOCKOUT
ALARM 06 (fig.4/b)
If the flame control has not detec-
ted thepresence of theflameafter a
completeignitionsequence,orforany
otherreasonthecardcannot“see”the
flame,theboilerwillstopandthedi-
splaywillshowthealarm“AL 06”.
Press the key
1
2
3
4
of the controls to
startuptheboileragain.
– SAFETY THERMOSTAT ERROR
ALARM 07 (fig.4/c)
If the C.H. sensor (SM1/SM2) exce-
edsthe100°Ctheboilerdoesnotigni-
tetheburner,thedisplayshowAL07
and remains ignited the green led. If
this condition persists for more than
oneminute,theboilerwillstop,thedi-
splayshowalwaystheanomalyAL07
andswitchontheredled.
Press the key
1
2
3
4
of the controls to
startuptheboileragain.
– FLAME DETECTION ERROR
ALARM 08
Iftheflamecontrolsectionrecognises
thepresenceofflamesinphaseswhen
they should not be present, it means
thereisabreakdownintheflamede-
tectioncircuit;theboilerwillstopand
thedisplaywillshowanomaly“AL 08”.
Fig.4/a
1
2
3
4
1
2
3
4
1
2
3
4
Fig.4
Fig.4/b
Fig.4/c
04
13
2
bar

Table of Contents

Other manuals for Sime FORMAT DGT 30e

Related product manuals