EasyManuals Logo

Sime FORMAT DGT 30i User Manual

Sime FORMAT DGT 30i
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
31
press
1
2
3
4
until
appears.
Confirmthisvalueusing
1
2
3
4
or
1
2
3
4
.
Exittheparameterssectionby pressing
1
2
3
4
.
The table below gives the values to set
whenthesupplygasischanged:
6.4.2.2 Adjusting valve pressure
(fig. 24)
Setmaximumandminimumpressureon
gasvalvesasfollows(fig.24):
– Connect a manometer to the intake
downstream of the gas valve (4 fig.
22).
Disconnect the valve VENT pressure
test point tube (5 fig. 22).
– Removethecap(1)fromthemodula-
tor.
- Puttheboilerinchimneysweepmode
(see section 6.4.4.2), ensure that ane
zonevalvesareopen.
– Pressthekey
1
2
3
4
(Hi).
- Turning the gas valve adjusters
clockwisewilldecreaseit.
- Adjust maximum pressure using the
nut(3)withawrenchtothemaximum
pressure valve indicated in Table 4
(fig.22).
– Adjust themaximumpressure before
adjustingtheminimum.
– Pressthekey
1
2
3
4
(Lo).
– Hold the nut (3) in place, turn the
screw (2) to the minimum pressure
indicatedinTable 4.
– Alternatelypressthekeys
1
2
3
4
and
1
2
3
4
and check that the maxi-
mumandminimum pressures corre-
spond to the set values; if necessary
readjust.
– Pressthekey
1
2
3
4
againtoquitthefun-
ction.
– RefitthevalveVENTpipe.
– Remove the manometer, remembe-
ring to tighten the screw for closing
thepressuretestpoint.
– Put the plastic cap (1) back on the
modulator. Check all test points and
connectionsforgastightness.
6.4.3 DISMANTLING
THE CASING (fig. 25)
The casing may be removed complete-
ly to facilitate boiler maintenance, as
showninfig. 25.Turn thepanel control
forwardforaccess totheinternal com-
ponentsoftheboiler.
6.4.4 MAINTENANCE
To guarantee functioning and efficien-
cy of the appliance, in respect of the
legal provisions in force, it must be
regularly checked; the frequency of the
checks depends on the type of instal-
lation and usage but this should be at
least annually.
Carry out the following procedure for
cleaningtheburner/heatexanger:
– Isolate the boilers electrical supply
andclosethegasisolationvalve.
– Removethe outercasingasshownin
fig.25;removethecombustioncham-
bercoverandtheburnercover.
– Idealyuseavacuumcleanerandasoft
brushtoremoveanydebris;takecare
nottodamagetheinsulationpanel.
- Clean the heat exchanger, removing
anydustorresiduefromcombustion.
- Whencleaning theheat exchangeror
theburner,chemicalproductsorsteel
brushesMUSTNOTBEUSED.
6.4.4.1 Ignition/Detection
electrode (fig. 27)
- Remove the casing, front panel and
sealedchambercovers.
- Unscrewthescrewsecuringtheelec-
trodeandremovefromtheburner.
- disconnecttheelectrodecable.
- Replacetheelectrodeandsetthegap
asshown.
3
2
1
Fig.24
KEY
1 Plastictap
2 Minimumpressureadjustingnut
3 Maximum pressure adjusting
nut
BOILER GAS MODELS PAR 1
METHANE 30 02
 30 i
 
30 e
LPG 30 04
1
2
4 x
Fig.25
Codice/Code 8109292
Modello/Model FORMAT DGT 30 i
Matricola/Serial n. 9999999999
PAR 1 = 02 (NG)/ 04 (LPG)
PAR 2 = 09
1
2
3
4
IGNITION/DETECTION
ELECTRODE
4±0,5
Fig.27

Table of Contents

Other manuals for Sime FORMAT DGT 30i

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sime FORMAT DGT 30i and is the answer not in the manual?

Sime FORMAT DGT 30i Specifications

General IconGeneral
BrandSime
ModelFORMAT DGT 30i
CategoryBoiler
LanguageEnglish

Related product manuals