CHART 2
IF END VOLTAGE READING OF BATTERY IS:
11.8V or more
11.7v to ll.OV
10.9 or less
* Retest battery after charging.
INSTRUCTIONS
Put in Service (See Note 1)
l
Charge Battery (See Note 1)
Discard Battery (See Note 2)
Note 1: Discard if battery has been in service for four or more years (dispose of properly).
Note 2: Dispose of properly.