Page 24 of 60 
 
 
Pre-4100U Series Fire Panels (4100+, 4100A) – The older Simplex 4100 Series Fire panels have the ability to 
detect Positive/Negative Earth Ground Faults. Unlike the 4100U Series Fire panels, their Power Supplies do not 
have the option to automatically diagnose on which circuit the fault is located. There are, however, methods which 
can narrow down the circuits in question.  
 
To begin, when the Earth fault is currently active on the fire panel:  
  Disconnect the power & comms to the different bays – power down the panel first (sequentially, and one 
at a time) until the Earth Fault clears from the system  
  After locating which bay of cards holds the problem, you will need to disconnect individual cards using the 
same methodology.  
  Once the card in question is located,  you will need to test the circuits but keep in mind the fault may be 
with the card, but is more likely is out in the field.  
  The motherboard that the card plugs into can be the source of the Earth Fault – the protection devices on 
the motherboard can fail after repeated discharges through them. 
  When the earth fault is located on a Mapnet or IDNet loop, disconnect one end of the loop from the Loop 
card (both + and - terminals), and break the loop in different areas (i.e. line isolators for example) until the 
Earth Fault disappears.  
 
NOTE – It is possible for Earth Ground Faults to switch from Positive to Negative Earth Ground Faults (or Vice-
Versa), so when disconnecting circuits it is highly recommended that you remove BOTH the positive and negative 
connections for efficient diagnosis. 
 
If you find that all the bays have been checked, and the earth fault appears to be in the main CPU Bay, the Earth 
fault  will  most  likely  be  on  the  Auxiliary  Fuse  Distribution  Board.  The  Auxiliary  fuse  card  should  be  unmounted 
(remove  4  screws)  &  insulate  the  Fuse  Card  from  the  mounting  studs  with  paper  or  cloth.  If  the  Earth  fault 
disappears, then the fault lies in the fuse card, otherwise you will need to individually disconnect each of the 24V 
power  supplies  from  the  Fuse Distribution  Board  in  turn,  narrowing  the circuit  with  the  Earth  Fault. If  the Earth 
Fault still remains, the fault is in the PSU 
 
 
 
PLEASE NOTE – Intermittent Earth Faults can only be diagnosed whilst the fault is active.