Page 52 of 60 
 
 
5.6  WIP Line Fault 
 
The WIPS2000 must connect to a WTRM2000 termination module. The WIPS9004 must connect to a WTRM9007 
termination module. Do not swap them over. 
 
 
 
NOTE:  WIP  Line  fault  LEDs  will  flash  (whilst  un-acknowledged)  when  a  WIP  Line  fault  is  detected  in  its 
corresponding  Zone.  For  example,  a  flashing  WIP  Line  Fault  LED  on  Zone  2  will  indicate  a  WIP  Line  fault 
associated with that Zone.  
 
A WIPS  Module  Fault  may  be  present  if  one  or  more  WIP  Line  Fault  LEDs  are  active.  The  zones  in  fault  will 
indicate will indicate which WIP Module may be having issues/problems, as the lines in fault will be connected to 
this module. 
 
If a WIP Line Fault is detected, you will need to check the wiring configuration (as above) and ensure the correct 
EOL  (end  of  line)  resistor  has  been  installed.  A WIP  Line  fault  indicator  LED  will  be  located  on  the  ECP  in  its 
corresponding Zone, depicting which WIP connection to focus on.