Page 18 of 60 
 
 
1.1.3.1.6  Output Abnormal 
 
Description: 
 
Observed when the output of a Relay, Sounder or Isolator base is not responding correctly. 
 
 
Possible causes: 
 
  ISOLATOR Base 
  A  Short  circuit  has  occurred  on  the  addressable  loop  and  the  Isolator  Base  has  not  been  able  to 
reset correctly  
 
  SOUNDER or RELAY Base 
  24 Volt supply to Sounder base is not present  
 
 
Suggested solutions: 
 
  ISOLATOR  Base  –  If  short  circuit  fault  has  been  corrected  press  „CPU  RESET‟  (Warm  Start)  to 
reinitialize the isolator base 
 
  SOUNDER or RELAY Base - Check wiring and 24V fused distribution board in panel 
1.1.3.1.7  Alarm Verification Tally Exceeded 
 
NOTE:  This  fault  indicates  a  dirty  detector  in  the  field  or  conventional  zone  circuit  that  is 
programmed for Alarm Verification. Check for previous faults and note in the Log book the 
time and date this fault occurred. 
 
1.  Log in at Level 4 
2.  Select P214 
3.  Force Point ON 
4.  Reset CPU (use button on CPU – refer to Page 7) to clear Simplex® Service Fault 
1.1.3.1.8  Detector LED Operation 
 
Off  
  Detector is not communicating with the Panel 
  Two Detectors on the same address 
  The Head is not fitted correctly 
 
Flash  
  Detector is communicating with the panel 
  Flash speed does not provide any information 
 
On  
  Detector is in ALARM or FAULT 
  If no Head fitted then EXTRA DEVICE fault. 
  Detector LED may become latched on if multiple faults occur to the same detector. To Reset 
the LED, move the Loop Card DIP Switch 1 to OFF for 10 seconds & back ON.  
  If all else fails, warm boot the fire panel (CPU Reset). 
 
1.1.3.1.9  Device DIP Switch Settings